Review finds sprinkler, egress and accessibility gaps in Coryell County courthouse
Summary
The Architexis assessment identifies missing fire sprinklers, nonconforming stair clearances and restroom layouts that no longer meet ADA standards; the consultant recommended fire‑sprinkler installation and adding accessible restrooms on multiple floors.
Get email alerts on the Code Compliance Accessibility topic
No spam. Unsubscribe anytime.
Architexis consultant Alexis McKinney told the court the building has several code‑compliance issues: it lacks a fire sprinkler system, some stair clearances fall below modern exit requirements, and restrooms renovated in 1987 no longer meet current ADA standards.
McKinney recommended adding a fire sprinkler system to improve egress viability and safety, and showed programming layouts to add accessible restrooms on the first and second floors (in addition to one in the basement). She explained that converting some spaces to ADA‑compliant restrooms may reduce overall fixture counts and that the master plan will include drawings and options for restroom placement.