Board presses for clearer photometric plans; staff to approve lighting administratively with bump‑back option
Summary
Board members expressed concern about uneven and code‑noncompliant lighting levels in the proposed plans and asked staff and the applicant for more detailed photometric information; staff said lighting could be approved administratively if it meets code, otherwise it will return to the board.
Get email alerts on the Lighting topic
No spam. Unsubscribe anytime.
Board members raised multiple questions about the proposed lighting for the multi‑building site, noting unclear photometric plans and examples where proposed fixtures exceeded code limits. Staff cited Section 153.173 and Guideline 6.7 as the applicable standards and said several proposed lamps did not meet uniformity or maximum/minimum foot‑candle requirements.
"Section 153.173 contains all lighting requirements and then Guideline 6.7 also apply," a staff member said during the lighting presentation, and later warned that some locations showed up to 35 foot candles where code allows up to 3. The applicant's representative, Tim Bass, said, "We have an electrical engineer that ... has agreed to work with staff with us and get the changes taken care of." Staff told the board that if staff and applicant cannot resolve issues or if a waiver is needed, the administrative approval can be bumped back to the board for further review.