Engineers urge replacement of shallow and corroded distribution mains on Vista, Airport and Winifred avenues

Seldovia City Council · July 28, 2026
AI-Generated Content: All content on this page was generated by AI to highlight key points from the meeting. For complete details and context, we recommend watching the full video. so we can fix them.

Summary

The 65% PER flags shallow burial, corrosion and dead‑end configurations on Vista, Airport and Winifred avenues; CRW recommended replacing several segments (including upgrading Vista to 8‑inch main for fire flow) and relocating Airport Avenue main into its right‑of‑way.

CRW engineers identified multiple distribution main deficiencies that cause repeated freezes, leaks and water‑quality issues: Airport Avenue's main is too shallow and out of the right‑of‑way, Winifred Avenue has multiple leaks creating dead ends, and Vista Avenue's corroded 6‑inch main has repeated leaks and sewer conflicts.

CRW recommended replacing Airport Avenue main in its right‑of‑way (rather than insulating in place), converting Vista Avenue to an 8‑inch main to restore adequate pressure and fire flow, and completing Winifred looping or replacement to address frequent leaks. Councilmembers had no objection to these priorities and asked staff to rank them in advance of the 95% PER.