Council hears utility briefing on interconnection risks and options for added generation
Aug 4, 2026
A utility representative warned that adding local generation can create "unintentional islanding" and outlined mitigation options — curtailment schemes, grounding transformers at each interconnection, or direct‑trip transfer schemes using fiber; an impact study fee increase was also noted.
The full story
A utility representative briefed the council on technical and safety issues tied to adding new generation to the local system. The representative said that if the upstream substation breaker opens, local generators can become an "unintentional island" at low load, which can lead to ground‑fault voltage and damage. To mitigate that risk, the representative explained options including curtailment schemes, installing grounding transformers at each interconnection point, or using a direct‑trip transfer scheme with fiber communications to isolate local generation before an upstream breaker opens.